Skip to content
Back to skills

Taiwan Telecom Design Codes

ASecurity

This skill should be used when checking indoor/outdoor telecommunication equipment setups, including telecom room sizes, lead-in conduits, shafts, and distribution boxes. Trigger words: 電信室、弱電間、引進管、總配線箱、電信管道。

  • 153 stars
  • 0 votes
  • 0 copies
  • 0 views
  • Added September 5, 2026
devops

Security analysis

A100/100

Pro scans all 2 files and shows the line behind each finding

Scanned September 5, 2026

npx -y skills add h30190/HJPLUS_Taiwan_Architect_KB --skill taiwan-telecom-design-codes --agent claude-code

Installs into .claude/skills of the current project.

Are you the author of Taiwan Telecom Design Codes?

Add the live security badge to your README. It updates with every re-scan.

Security grade badge for Taiwan Telecom Design Codes
[![Security: A — Skills Directory](https://www.skillsdirectory.com/api/skills/h30190-taiwan-telecom-design-codes/badge)](https://www.skillsdirectory.com/skills/h30190-taiwan-telecom-design-codes)

More formats (shields.io, HTML) on the badges page. Keep it an A: scan every change in CI with Pro.

Download with Pro
SKILL.md
---
type: Skill
name: taiwan-telecom-design-codes
description: "This skill should be used when checking indoor/outdoor telecommunication equipment setups, including telecom room sizes, lead-in conduits, shafts, and distribution boxes. Trigger words: 電信室、弱電間、引進管、總配線箱、電信管道。"
metadata:
  class: C
---

# Taiwan Telecom Equipment Installation Codes

## Context & Purpose
This skill encapsulates the NCC "Indoor and Outdoor Telecommunication Equipment Installation Technical Specifications" (屋內外電信設備設置技術規範) in Taiwan, covering critical space and conduit requirements for telecom infrastructure.

## Parameters & Constraints

### 1. Telecom Room Area Sizing (電信室面積計算)
- Telecom rooms are required for buildings meeting specific thresholds (e.g., based on total floor area or number of households).
- Minimum size limits exist based on building type (e.g., minimum 1.5 m² or 2.0 m² up to much larger areas for commercial complexes).
- The room MUST NOT share space with water tanks, transformer rooms, or any area prone to flooding or strong electromagnetic interference.

### 2. Lead-in Conduits (電信引進管)
- Minimum requirement: At least **2 conduits** must be introduced into the building (1 active, 1 spare).
- For larger buildings, specific diameter and quantity formulas apply (typically 80mm or 100mm PVC/HDPE pipes).

### 3. Telecom Shafts (電信管道間)
- Must be vertically aligned and independent.
- **Prohibited**: Water supply pipes, drainage pipes, and fire sprinkler pipes MUST NOT pass through the telecom shaft.

### 4. Home Distribution Box (宅內配線箱)
- Each household must have a dedicated distribution box.
- Must be equipped with at least one **110V AC power outlet** to power networking equipment (modems, routers).
- Installation height: Usually between 30 cm and 150 cm from the floor finish level, avoiding areas prone to moisture.

## Execution Logic for AI
When reviewing telecom plans:
1. Verify the presence of a dedicated telecom room if the building size dictates it.
2. Check the number of lead-in conduits (must be ≧ 2).
3. Validate that telecom shafts do not contain any plumbing pipes.
4. Ensure home distribution boxes include a 110V power receptacle.