IEC 61131-3 programming languages reference (LD, FBD, ST, IL, SFC), PLCopen standards, program organization units, data types. Use when discussing PLC programming standards or cross-platform compatibility.
Scanned 9/8/2026
Install to Claude Code
npx -y skills add claude-dev-suite/claude-dev-suite --skill iec61131 --agent claude-codeInstalls into .claude/skills of the current project.
Are you the author of Iec61131?
Add the live security badge to your README — it updates automatically with every re-scan.
[](https://www.skillsdirectory.com/skills/claude-dev-suite-iec61131)More formats (shields.io, HTML) on the badges page.
---
name: iec61131
description: IEC 61131-3 programming languages reference (LD, FBD, ST, IL, SFC), PLCopen standards, program organization units, data types. Use when discussing PLC programming standards or cross-platform compatibility.
user-invocable: false
---
# IEC 61131-3 Programming Languages Reference
## Overview
IEC 61131-3 defines 5 programming languages for PLCs, all interchangeable:
| Language | Type | Best For | Status |
|----------|------|----------|--------|
| LD (Ladder Diagram) | Graphical | Discrete logic, motor interlocks | Active |
| FBD (Function Block Diagram) | Graphical | Continuous control, PID, analog | Active (DCS primary) |
| ST (Structured Text) | Textual | Complex calculations, algorithms | Active (most expressive) |
| IL (Instruction List) | Textual | Low-level, assembly-like | Deprecated (3rd ed. 2013) |
| SFC (Sequential Function Chart) | Graphical | Sequences, batch, state machines | Active |
## Program Organization Units (POUs)
### PROGRAM
Top-level executable, associated with a task (scan cycle).
### FUNCTION_BLOCK (FB)
Reusable block with **persistent internal state** (memory between calls). Used for motors, PID, timers, counters.
```
FUNCTION_BLOCK MotorControl
VAR_INPUT
StartCmd : BOOL;
StopCmd : BOOL;
FbkRun : BOOL;
Interlock: BOOL;
END_VAR
VAR_OUTPUT
StartOut : BOOL;
Running : BOOL;
Fault : BOOL;
END_VAR
VAR
MonTimer : TON;
State : INT;
END_VAR
```
### FUNCTION (FC)
Stateless, no memory. Always returns same output for same input.
## Data Types
### Elementary
BOOL, BYTE, WORD, DWORD, LWORD, SINT, INT, DINT, LINT, USINT, UINT, UDINT, ULINT, REAL, LREAL, TIME, DATE, TIME_OF_DAY, DATE_AND_TIME, STRING, WSTRING
### Derived (User-Defined)
```
TYPE MotorData :
STRUCT
Running : BOOL;
Fault : BOOL;
Speed : REAL;
Runtime : TIME;
END_STRUCT
END_TYPE
```
## Variable Scopes
| Scope | Keyword | Description |
|-------|---------|-------------|
| Local | VAR | Internal to POU |
| Input | VAR_INPUT | Read-only input parameter |
| Output | VAR_OUTPUT | Output parameter |
| In/Out | VAR_IN_OUT | Bidirectional parameter |
| Global | VAR_GLOBAL | Accessible by all POUs |
| External | VAR_EXTERNAL | Reference to global |
| Temp | VAR_TEMP | No persistence |
| Config | VAR_CONFIG | Set at download |
| Constant | CONSTANT | Named constant |
## Language Details
### ST (Structured Text) - Most Relevant for Code Generation
```
IF Motor.FbkRunning AND NOT Motor.Fault THEN
Motor.Status := RUNNING;
Motor.Runtime := Motor.Runtime + T#1s;
ELSIF Motor.Fault THEN
Motor.Status := FAULTED;
Motor.AlarmActive := TRUE;
END_IF;
CASE State OF
0: (* IDLE *)
IF StartCmd AND NOT Interlock THEN State := 1; END_IF;
1: (* STARTING *)
StartOut := TRUE;
MonTimer(IN:=TRUE, PT:=T#10s);
IF FbkRun THEN State := 2; END_IF;
IF MonTimer.Q THEN State := 99; END_IF;
2: (* RUNNING *)
IF StopCmd THEN State := 3; END_IF;
3: (* STOPPING *)
StartOut := FALSE;
99: (* FAULT *)
StartOut := FALSE;
Fault := TRUE;
END_CASE;
```
### SFC (Sequential Function Chart)
Elements: Steps, Transitions, Actions
- Steps contain actions (in any language)
- Transitions are boolean conditions
- Action qualifiers: N (non-stored), S (set), R (reset), L (time limited), D (delayed), P (pulse)
- Parallel branches (simultaneous), Alternative branches (selective)
### FBD (Function Block Diagram)
Signal flow left-to-right. Blocks represent functions. Wires connect outputs to inputs. Primary language in DCS (PCS 7 CFC, DeltaV Control Studio, ABB Freelance).
### LD (Ladder Diagram)
Based on relay logic. Contacts (NO/NC), coils, timers, counters. Left/right power rails. Rungs top-to-bottom.
## PLCopen Standards
| TC | Topic | Description |
|----|-------|-------------|
| TC1 | Standards | IEC 61131-3 compliance testing |
| TC2 | Motion Control | MC_MoveAbsolute, MC_Stop, MC_Home, etc. |
| TC3 | Software Engineering | Coding guidelines |
| TC4 | Communications | OPC UA mapping |
| TC5 | Safety | IEC 61508 extensions |
| TC6 | XML Exchange | Vendor-neutral program interchange format |
## PLCopen XML Format (TC6)
```xml
<project xmlns="http://www.plcopen.org/xml/tc6_0201">
<types>
<pous>
<pou name="MotorControl" pouType="functionBlock">
<interface>
<inputVars>
<variable name="Start"><type><BOOL/></type></variable>
</inputVars>
<outputVars>
<variable name="Running"><type><BOOL/></type></variable>
</outputVars>
</interface>
<body>
<ST><xhtml><!-- Structured Text --></xhtml></ST>
</body>
</pou>
</pous>
</types>
</project>
```
Supported by: CODESYS, ABB AC500, Schneider, Beckhoff, B&R.
NOT supported by: ABB Freelance (uses PRT), Emerson DeltaV (uses FHX), Siemens (uses SimaticML).
## Other Exchange Formats
| Format | Standard | Used By |
|--------|----------|---------|
| PLCopen XML | IEC 61131-10 | CODESYS, Schneider, Beckhoff |
| SimaticML | Siemens proprietary | TIA Portal |
| AutomationML | IEC 62714 | Siemens PCS 7 V9+, multi-vendor |
| FHX | Emerson proprietary | DeltaV |
| PRT/CSV | ABB proprietary | Freelance |
| DEXPI | ISO 15926 | P&ID exchange |